HAESHaes MZAOV Zone Extension PCB TPCA028
Key features✓Fire alarm zone circuit, conventionally wired detection circuit or Twin wire combined detection / sounder circuit, monitored via a 6K8Ohms 5% 0.25W end-of-line resistor✓Monitoring current limit is 50mA, fused at 500mA; typical max load 22 devices, at 18mA each, in each zone circuit✓Alarm activating input, 2K7Ohms alarm; 6K8Ohms 5% 0.25W EOL resistor✓Monitoring current limit 1.5mA, unfused✓Dual polarity reversal actuator drive outputs, 28VDC maximum 8A✓Maximum inrush current of 20A for 2 seconds